Isolating amplifier

ST500 / TV500

Isolating signal converter for process control signals, converting 0/4 ... 20 mA or 0/2 ... 10 V DC inputs to selectable current and voltage outputs. 22.5mm DIN rail case, 3-port isolation and ST500 transmitter supply.

Introduction

Clean signal conversion helps process control systems work with dependable standard values from the field. TV500 isolates and converts 0/4 ... 20 mA or 0/2 ... 10 V DC input signals into industry standard outputs for control applications.
 
Front DIP switches allow quick selection of current or voltage ranges on site. The output can be configured for 0/4 ... 20 mA and 0/2 ... 10 V, with voltage output available simultaneously to the current output. A max. current output burden of 1 kΩ supports direct control of I/P transmitters and 20 mA proportional valves.
 
Full 3-port isolation separates input, output and supply, reducing unwanted interaction between connected circuits. The 22.5mm DIN rail case fits compact cabinet layouts, with supply voltage options of 100 ... 265 V AC or 10.8 ... 30 V AC/DC. Measuring range 10 offers T90 <20 ms, while measuring range 11 offers T90 <100 μs.

Flexible conversion
Flexible conversion
Switch selectable 0/4 ... 20 mA and 0/2 ... 10 V DC inputs and outputs.
Clean separation
Clean separation
Full 3-port isolation separates input, output and supply.
Direct actuator use
Direct actuator use
Current output supports max. 1 kΩ burden for I/P transmitters and 20 mA valves.
Sensor feed included
Sensor feed included
ST500 provides an integrated approx. 24 V DC transmitter supply.

Features

Switch selectable inputs

The input range is configured on the front panel for 0 ... 20 mA, 4 ... 20 mA, 0 ... 10 V DC or 2 ... 10 V DC.

Current and voltage outputs

The output can be selected for 0 ... 20 mA, 4 ... 20 mA, 0 ... 10 V or 2 ... 10 V, with current and voltage output available simultaneously.

Transmitter supply

ST500 versions provide a fully floating isolated transmitter supply for connected field devices.

Supply voltage variants

Versions are available for 100 ... 265 V AC or 10.8 ... 30 V AC/DC auxiliary voltage.

Response time options

Measuring range 10 provides T90 <20 ms. Measuring range 11 provides T90 <100 µs for faster signal transmission.

Adjustment controls

The measuring range and 4mA/2V value can be adjusted by approx. +/-5% using front panel controls.

DIN rail housing

The device uses a 22.5mm polycarbonate case for TH35 DIN rail mounting, with housing IP30 and terminals IP20.