Limit value switch for standard signal supervision

GWA-250-U0

Limit value switch for standard signal supervision evaluates 0...10V, 0...20mA or 4...20mA inputs, with two relay outputs, adjustable 0...99% limits and 20 to 253V AC / DC supply.

Introduction

Standard signals often need direct, dependable switching in the control cabinet. This limit value switch supervises 0...10V, 0...20mA or 4...20mA signals for underrun or transgression of set limits, allowing up to two switching limits without additional measuring devices.
 
It is well suited for supply and control voltage supervision, including filling level monitoring and pump control in water and waste water applications. Limit values are set as 0...99% of the configured signal range in 1% steps, giving technicians a clear, fast way to adapt switching points on site.
 
Two potential-free changeover relays support double limit value operation or two-position control with hysteresis. Configurable 0.4 s or 4 s switching delay helps prevent unwanted relay actions caused by signal fluctuations, while the 20 to 253V AC / DC wide-range supply supports use in common control cabinet power systems.

Standard signal fit
Standard signal fit
Evaluates 0...10V, 0...20mA and 4...20mA inputs.
Two relay limits
Two relay limits
Two changeover relays allow two separated switching limits.
Simple adjustment
Simple adjustment
Key coding switches set limits from 0...99% in 1% steps
Stable switching
Stable switching
0.4 s or 4 s delay helps compensate signal fluctuations.
Wide supply range
Wide supply range
20 to 253V AC / DC supply supports common cabinet systems.

Features

Standard signal input

The device compares a connected 0...10V, 0...20mA or 4...20mA signal with the configured limit value.

Relay operation modes

The relay outputs can be configured for double limit value function or two-position control with hysteresis.

Safety function

Minimum safety or maximum safety can be set separately for each relay output.

Measurand transducer supply

The connected signaling transmitter or measuring transducer can be powered by the integrated overload and short-circuit protected supply.

Signal scaling

Limit values are referenced to the nominal signal range and the respective signal zero value, depending on the selected input signal.

DIN rail housing

The device is designed for vertical installation on DIN EN 60715 TH 35-7.5 or TH35-15 standard rails.

Galvanically isolation

Power supply input, measuring input and relay output channels are galvanically isolated from each other.