Humidity transducer for wall, duct and open-air monitoring

GRHU

Humidity transducer for wall and duct humidity monitoring, measuring 0.0 ... 100.0 % RH with temperature compensation, 4-20 mA standard output, 4-digit LCD and IP65 ABS housing.

Introduction

Humidity control depends on readings that fit the installation point, not only the measuring range. GRHU variants support wall mounting, duct installation, separated probe placement and open-air measurement with the heat absorption hat, giving planners one transmitter family for several monitoring layouts.
 
The transducer measures 0.0 ... 100.0 % RH with automatic temperature compensation. At 25 °C and within the recommended range, humidity accuracy is ±2.5 % RH, while the sensor head and tube cover -40 ... +100 °C, with short-term use up to 120 °C. This gives operators a clear technical basis for room, duct and outdoor humidity monitoring.
 
Setup remains practical on site. The device includes min/max memory, adjustable offset and slope, and scalable output. A 4-20 mA output is standard, with 0-10 V and 0-1 V analog options. The ABS housing and EN 175301-803/A elbow-type plug are rated IP65.

Mounting choice
Wall, duct, separated probe and weather shield versions fit room, duct and open-air measurement.
Full humidity range
Measures 0.0 ... 100.0 % RH with automatic temperature compensation.
Clear signal output
4-20 mA is standard, with 0-10 V and 0-1 V analog output options.
IP65 protection
ABS housing and EN 175301-803/A elbow plug are rated IP65.
Simple setup
Min/max memory, offset and slope adjustment, and scalable output support commissioning.

Features

Display options

The 4-digit LCD alternates between humidity and temperature. With option UNI, the keyboard selects alternative values including wet bulb temperature, dewpoint temperature, enthalpy, atmospheric humidity or absolute humidity.

Sensor options

Standard and high humidity sensor options are listed. The high humidity option extends the recommended humidity range to 5.0 ... 95.0 % RH.

Probe lengths

 Sensor tube fitting lengths are available from 50 mm to 500 mm, with 50 mm standard for 1R and 220 mm standard for 1K and 2K versions.

Electrical supply

The device uses 12 ... 30 VDC, or 18 ... 30 VDC for 0-10 V output. Reverse voltage protection is specified at 50 V permanently.

Condensation option

An encapsulated PC board option is available where temperature changes create condensation risk in the electronics environment.