Humidity and temperature transducer for wall, duct and open-air use

GHTU

Humidity and temperature transducer for wall or duct applications, measuring 0.0 ... 100.0 % RH and -40.0 ... +120.0 °C with 4-20 mA standard output, LCD display and IP65 housing.

Introduction

Reliable humidity and temperature values are easier to trust when the transmitter is built for the installation point. GHTU variants cover wall and duct mounting, separated probe installation and open-air measurement with the optional heat absorption hat, helping you use the same product family across indoor, duct and weather-exposed tasks.
 
The measuring core covers 0.0 ... 100.0 % RH with automatic temperature compensation and sensor temperatures from -40.0 ... +120.0 °C. Accuracy at 25 °C in the recommended range is ±2.5 % RH and ±0.4 % of measuring value ±0.2 °C, giving operators a clear basis for monitoring and control decisions.
 
Commissioning stays practical on site. The transducer provides a 4-20 mA standard output, selectable voltage options, a 4-digit LCD display, min/max memory, adjustable offset and slope, and scalable output signals. The ABS housing and EN 175301-803/A elbow-type plug are rated IP65 for industrial environments.

Flexible mounting
Wall, duct, separated probe and weather shield versions support room, duct and open-air use.
Wide sensor range
Measures 0.0 ... 100.0 % RH and sensor temperatures from -40.0 ... +120.0 °C.
Process-ready output
4-20 mA is standard; 0-1 V and 0-10 V options are available.
Protected housing
ABS housing and EN 175301-803/A elbow-type plug are rated IP65.
On-site adjustment
Min/max memory, offset and slope adjustment, and scalable output support setup.

Features

Display values

The 4-digit LCD display alternates between humidity and temperature. With option UNI, an alternative value can be shown instead of humidity, including wet bulb temperature, dewpoint temperature, enthalpy, atmospheric humidity or absolute humidity.

Sensor versions

The family includes wall, surface/duct and duct designs. The cable version uses a separated sensor tube connected to the device via a 1 m teflon cable and includes the high humidity sensor option.

Probe lengths

 Fitting lengths are available for 50 mm, 220 mm, 300 mm, 400 mm and 500 mm sensor tubes, with 50 mm standard for surface design and 220 mm standard for surface/duct and duct designs.

Supply and protection

The auxiliary energy is 12 ... 30 VDC, or 18 ... 30 VDC for 0-10 V output. Reverse voltage protection is specified at 50 V permanently.

Sensor and board options

Standard and high humidity sensor options are listed. An encapsulated PC board option is available for applications with condensation risk caused by temperature changes.